Dear Tuners! November 11 to 30 I'll be on a business trip out of the office. All the orders placed during that period will be processed at the begining of December. I'll do my best to answer your messages at least twice a day, but I won't be available for remote desktop sessions.

Electric motor control (dyno cooling fan)

Variable Frequency Drive (VFD) control based on INVT Goodrive20 example

These are the two ways to control the VFD from PEREK dyno controller. One way is to use a relay and digital input to enable the inverter and analog signal to set the desired motor frequency. The other way is to send commands via RS485 interface. RS485 has more advantages over the previous method. Firstly, multiple VFDs can be connected only with a two-wire bus. Secondly, the commanded frequency is precise without any analog offsets on the signal. The third advantage is that INVT RS485 connection offers much more functionality, like setting up most of the VFD parameters or reading diagnostic values like the mains voltage. All the parameters transferred on the RS485 will be logged with the run data.

Electrical connection

The VFD can be connected via 4 wires to communicate desired frequency and enable drive.

The other, preferred way is to use a two-wire RS485 connection.

VFD configuration

Function codeNameDescriptionComments
P00.01Channel of running commands0: Keypad (“LOCAL/REMOT” light off)
1: Terminal (“LOCAL/REMOT” flickering)
2: Communication (“LOCAL/REMOT” on)
For “4-wire” communication set 1
For RS485 communication set 2
P00.06A frequency command section0: Keypad data setting
1: Analog AI1 setting (corresponding keypad potentiometer)
2: Analog AI2 setting (corresponding terminal AI2)
3: Analog AI3 setting (corresponding terminal AI3)
8: Modbus communication setting
For “4-wire” communication set 2
For RS485 communication set 8
P00.11ACC timeAcceleration timeThis value can be reduced from default to allow faster acceleration
P00.12DEC timeDeceleration timeThis value can be reduced from default to allow faster deceleration
P02.01 – P02.05Motor parametersFill all parameters using the motor nameplate
P05.01S1 terminal function selection0: No function
1: Forward running
2: Reverse running
For “4-wire” communication set 1
P05.37Lower limit of AI2Voltage on the AI2 input corresponding to 0% frequencyFor “4-wire” communication, calibrate to compensate analog signal voltage drops
P05.39Upper limit of AI2Voltage on the AI2 input corresponding to 100% frequency
P14.00Local communication addressSetting range: 1–247
When the master writes the slave
communication address to 0 indicating a
broadcast address in a frame, all the slaves on
the Modbus bus receive the frame but do not
respond to it.
Local communication address is unique in the
communication network, which is the basis for
point-to-point communication between the
upper computer and the VFD.
P14.01Communication baud rate0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
6: 57600BPS
The baud rate set on the VFD must be
consistent with that on the upper computer.
Otherwise, the communication fails. A greater
baud rate indicates faster communication.
P14.02Data bit check0: No check (N, 8, 1) for RTU
1: Even check (E, 8, 1) for RTU
2: Odd check (O, 8, 1) for RTU
3: No check (N, 8, 2) for RTU
4: Even check (E, 8, 2) for RTU
5: Odd check (O, 8, 2) for RTU
6: No check (N, 7, 1) for ASCII
7: Even check (E, 7, 1) for ASCII
8: Odd check (O, 7, 1) for ASCII
9: No check (N, 7, 2) for ASCII
10: Even check (E, 7, 2) for ASCII
11: Odd check (O, 7, 2) for ASCII
12: No check (N, 8, 1) for ASCII
13: Even check (E, 8, 1) for ASCII
14: Odd check (O, 8, 1) for ASCII
15: No check (N, 8, 2) for ASCII
16: Even check (E, 8, 2) for ASCII
17: Odd check (O, 8, 2) for ASCII
The data format set on the VFD must be
consistent with that on the upper computer.
Otherwise, the communication fails.

Currently, the RTU formats are supported.
INVT settings
Baud rateMax. transmission distance
2400 BPS1800m
4800 BPS1200m
9600 BPS800m
19200 BPS600m
Baud rate vs max transmission distance
Modbus addressData meaningR/W
2000H0001H: Forward running
0002H: Reverse running
0003H: Forward jogging
0004H: Reverse jogging
0005H: Stop
0006H: Coast to stop
0007H: Fault reset
0008H: Jogging to stop
R/W
2001HCommunication setting frequency
(0–Fmax (unit: 0.01Hz))
R/W
2102HFault code of the VFDR
3002HBus voltage 0.0-2000.0VR
3003HOutput voltage 0.0–1200.0VR
3004HOutput current 0.0-3000.0AR
Modbus address description

The tables above represent only a part of the settings and commands that are relevant to typical needs. The whole INVT manual can be found here:

More information on Modbus protocol:

Dyno2 configuration

Dyno2 Dynamometer Software – user interface input channels

Dyno2 Dynamometer Software – custom functions

Dyno2 Dynamometer Software – Modbus

Dyno2 Dynamometer Software – working in run tab

Fan control strategy ideas

  1. Simple manual control – the fan speed is set manually by you. It can be from a widget in RUN tab, from a potentiometer connected to an analog input on dyno controller, etc.
  2. Road speed based control – the fan speed is a function of dyno speed. This can be used to simulate road conditions.
  3. Power based control – the fan speed is a function of power received by the dyno. The vehicle is automatically cooled under load.
  4. Intake air based control – the fan speed is a function of intake air temperature. This will prevent the intake manifold from heat soaking when idling before run.
  5. Combined control – for example, the final fan speed is maximum from idea 1, 2, 3 and 4. This is a simple and effective way to provide adequate cooling for the vehicle during power runs with the convenience of manually overriding minimal fan speed.
  6. Coolant temperature PID control (sensor attached to radiator) – in this method, it’s best to place an additional temperature sensor just after the radiator and use it as feedback for PID. Setpoint should be set manually in the user interface to suit the vehicle you’re currently working on. This method provides perfect control of engine temperature for maximum repeatability between runs.
  7. Coolant temperature PID control (OBD or CAN) – simplified way to control engine temperature is to use OBD or CAN bus information about engine temperature. With this method, you don’t need to attach the extra sensor, but the engine thermostat can mess up with PID control. Also, the control loop delay is quite long, which makes PID tuning quite time-consuming.

Here are some videos from idea 7 tests: